TRUESAFE™ Chemical Earthing manufactured by SG Power Products Pvt. Ltd. is a high-quality Copper Bonded Rod designed for efficient electrical grounding applications. This model features a 14 mm diameter rod with 2 metre length, providing reliable current dissipation and long service life in earthing systems.
The rod is manufactured using E250 grade steel core with a copper bonded layer for superior conductivity and corrosion resistance. It complies with IS3043 standards and is supplied with SS Clamp clamp for secure electrical connections. This rod is UL & CPRI tested.
Datasheet (PDF)| Manufacturer | SG Power Products Pvt. Ltd. |
| Product | TRUESAFE™ Chemical Earthing |
| Model | CBR14SG200 |
| Make | SGPL |
| Material Description | Copper Bonded Rod |
| Dia of Rod | 14 mm |
SG Power Products Pvt. Ltd., based in Noida (Delhi NCR), is a UL listed copper bonded rod manufacturer in India, with copper bonded ground rods listed to UL 467 under UL File No. E511876. Every rod has a minimum copper coating of 254 microns (10 mils). The rods are made at our Duhai Industrial Area factory in Ghaziabad, Uttar Pradesh, and are certified by UL for both the US (UL 467) and Canada (CSA C22.2 No. 41). As a direct UL listed copper bonded rod supplier, we support EPC contractors, consultants and owner's engineers on projects where the specification calls for UL listed grounding electrodes.
SG Power has supplied earthing and lightning protection materials for over 15 years to organisations including Indian Railways, L&T, NTPC, BHEL, Tata, Adani Power and the Airport Authority of India.
| Item | Detail |
|---|---|
| Standards | UL 467, Edition 11 (2022), Grounding and Bonding Equipment (US); CSA C22.2 No. 41:22 (Canada) |
| UL File No. | E511876 |
| UL category | KDER (US) and KDER7 (Canada), Grounding and Bonding Equipment |
| Listed models | SGPCBR-1403, SGPCBR-1703, SGPCBR-2003, SGPCBR-2503 |
| Verify online | Search E511876 in UL Product iQ |
| Listed sizes | 14, 17, 20 and 25 mm diameters |
| Copper coating | 254 microns (10 mils) minimum, molecularly bonded to a low-carbon steel core |
| Manufactured at | Plot No. 695-696, Duhai Industrial Area, Ghaziabad, Uttar Pradesh 201206 |
| Detail | What you get |
|---|---|
| Listed sizes | 14, 17, 20 and 25 mm diameters (UL File No. E511876) |
| Copper coating | 254 microns (10 mils) minimum, meeting UL 467 |
| Delivery | Pan-India, direct to project sites |
| Documents | UL certificates (US and Canada), datasheet and test certificates for submittal |
A UL listed copper bonded rod is a copper bonded earth rod that UL (Underwriters Laboratories) has tested and certified to UL 467, and whose maker is under UL's ongoing follow-up inspection. The rod has a high-tensile, low-carbon steel core with electrolytic copper molecularly bonded to its surface. The steel gives strength for driving; the copper gives conductivity and corrosion resistance.
In specifications and on site, the same product is also called a UL listed copper bonded ground rod, grounding rod, earth rod, earthing rod or copper bonded grounding electrode. Indian specifications usually say "earthing", while specifications based on US standards say "grounding".
"Listed" means more than "tested once". UL checks the product against the standard, records it under a file number, and audits the factory periodically. A rod described only as "conforming to UL 467" or "UL 467 grade" has not necessarily been through that process.
Buyers often search for "UL approved" or "UL certified" copper bonded rods. UL does not "approve" products; it tests and lists them. On a specification or purchase order, the correct term for ground rods is UL listed, followed by the UL file number.
UL 467 sets requirements for grounding and bonding equipment, including ground rods. The current edition is Edition 11, issued 29 April 2022, and it is the edition SG Power's rods are certified to. For copper bonded rods, the checks typically include:
Copper coating thickness and how firmly it is bonded to the steel
Adhesion: the copper must not peel or crack when the rod is bent or driven
Dimensions: diameter and length within tolerance
Marking: each rod carries the maker's name or mark, the UL mark and its size, so it can be identified on site
For Canada, the matching standard is CSA C22.2 No. 41, Grounding and Bonding Equipment. UL lists products certified to it under category KDER7, so one UL file can cover both countries, often shown as the cULus mark.
Many US-based specifications also cite ANSI/NEMA GR 1, the product standard for grounding rod electrodes and couplings, alongside UL 467. Manufacturer datasheets for listed rods commonly reference both.
Indian projects normally design earthing to IS 3043. UL listing comes in when the project specification follows US standards, such as the NEC (NFPA 70), or when the owner's global engineering standard requires UL listed grounding. Many projects use both: earthing designed to IS 3043, with UL listed rods as the electrodes.
| Specification basis | Typical projects in India | Rod requirement |
|---|---|---|
| IS 3043 only | Domestic utilities, government, commercial buildings | Copper bonded rods to IS 3043; UL listing not required |
| NEC / NFPA 70 or owner's US-based standard | Data centres, US and multinational owners, oil and gas | UL listed rods, by file number |
| IS 3043 design with UL listed electrodes | Multinational factories, EPC projects for global owners | UL listed rods, installed to the IS 3043 design |
| Advantage | Engineering basis | Procurement impact |
|---|---|---|
| Third-party certification | Tested by UL to UL 467; periodic factory follow-up | Fewer submittal queries; no separate type-test demand |
| Minimum copper thickness | 10 mils (0.254 mm) minimum for UL listed rods | Defined coating, checkable against the listing |
| Bond integrity | Copper electrolytically bonded to steel; listing tests check adhesion | Lower risk of coating damage during driving |
| Mechanical strength | High-tensile, low-carbon steel core | Suitable for deep driving and coupled sections |
| Corrosion resistance | Copper protects the steel core in moist and saline soil | Lower replacement and re-excavation cost |
| Traceability | UL mark, maker's mark and size within the top 12 in (305 mm) | Easy incoming and post-installation inspection |
| Cost compared with solid copper | Steel core with copper surface | Lower unit price than solid copper rods |
SG Power makes UL listed copper bonded rods in four types, so you can match the rod to your soil depth and connection method.
Rolled threads at both ends; joined with couplers to reach the depth the design needs. Used for substations, data centres and high-resistivity soil.
View threaded rodsA single-length rod with a pointed end, driven in one piece with no couplers. Used where one rod length meets the target resistance, such as buildings, telecom shelters and solar arrays.
View unthreaded rodsA flat palm terminal on top gives a fast, bolted conductor connection that can be inspected, without welding.
View palm variantSupplied with a ground clamp for round conductors or cables, for equipment and lightning protection earthing.
View clamp variant| Type | Joining | Best for | Typical depth |
|---|---|---|---|
| Threaded (sectional) | Couplers between rods | Deep earthing, high-resistivity soil, substations, data centres | Multiple rod lengths |
| Unthreaded (pointed) | None, single piece | Buildings, telecom, solar arrays | One rod length |
| With palm terminal | Bolted palm connection | Quick, inspectable connections | One or more rods |
| With clamp | Clamp to conductor | Equipment and lightning protection earthing | One or more rods |
Choose the rod from your project specification and site data, not from a fixed rule. Check these six points in order.
Read the earthing clause of your project specification. If it names UL 467 or "UL listed", you need a rod with a UL file number. If it only names IS 3043, a standard copper bonded earth rod may cost less.
Measure soil resistivity at the site; the target earth resistance comes from the project design and applicable standard. Low-resistivity soil may meet the target with one rod. High-resistivity or rocky soil, and low targets such as substations and data centres, usually need deeper threaded rods, several rods in parallel, or backfill compound.
| Site condition | Suggested diameter |
|---|---|
| Soft or normal soil, shorter depths | 5/8" |
| Hard or stony soil, deep driving, heavy-duty sites | 3/4" |
A thicker rod resists bending when driven hard. Diameter has only a small effect on earth resistance; depth matters more.
One rod length meets the target → unthreaded (pointed) rod
Target needs more depth → threaded rods with couplers, extended until the target is met
Space for several rods → rods in parallel, spaced as IS 3043 advises so they do not reduce each other's effect
Fast bolted joint you can inspect → rod with palm terminal
Round conductor or cable → rod with clamp
Permanent, maintenance-free joint → exothermic weld
If the specification asks for a fully listed system, choose couplers and clamps that are UL listed too.
Confirm that the exact diameter and length you order appear under UL File No. E511876 in Product iQ. SG Power's listed models are SGPCBR-1403 (14 mm), SGPCBR-1703 (17 mm), SGPCBR-2003 (20 mm) and SGPCBR-2503 (25 mm); ask for the model number on the quotation. A custom size outside the listing is not UL listed.
| Application | Suggested rod |
|---|---|
| Data centre or substation | 3/4" threaded rods with listed couplers, driven to design depth |
| Commercial building | 5/8" unthreaded rod, or threaded if soil is poor |
| Solar array | 5/8" unthreaded rods at each array earth point |
| Telecom shelter | 5/8" or 3/4" rod with clamp |
| Rocky or hard ground | 3/4" rod, with backfill compound where depth is limited |
Need a design check? Share soil resistivity data, prospective fault current and target earth resistance. Our application engineers will propose rod type, size, depth and quantity against your specification.
The rod may look the same, but only a listed rod comes with proof a consultant can verify.
| Feature | UL listed copper bonded rod | Non-listed copper bonded rod |
|---|---|---|
| Third-party certification | Certified by UL to UL 467 | Usually maker's own test claim |
| Verifiable online | Yes, by UL file number in Product iQ | No public record |
| Factory follow-up | Periodic UL inspections | None from UL |
| Marking on rod | UL mark, maker, size | Varies by maker |
| Accepted where UL is specified | Yes | Usually rejected at submittal |
| Canadian certification | Available where listed to CSA C22.2 No. 41 (category KDER7), as SG Power's rods are | No |
| Typical use | Data centres, oil and gas, US-standard and multinational projects | General commercial and domestic earthing |
| Price | Higher | Lower |
If your specification does not call for UL listing, our standard copper bonded earth rods built to IS 3043 may be more economical. That page also compares copper bonded rods with GI, solid copper and stainless steel rods.
Every diameter below is covered by UL File No. E511876 (models SGPCBR-1403, 1703, 2003 and 2503), with a minimum copper coating of 254 microns (10 mils). Prices are indicative per piece, ex-works, and vary with quantity.
| Rod (UL model) | Diameter | Length | Copper coating | Price from |
|---|---|---|---|---|
| UL Listed Copper Bonded Rod 5/8" x 8 ft (SGPCBR-1403) | 5/8" (14.2 mm shank) | 2.4 m | 254 µm (10 mils) min. | Depend on LME Price |
| UL Listed Copper Bonded Rod 5/8" x 10 ft (SGPCBR-1403) | 5/8" (14.2 mm shank) | 3.0 m | 254 µm (10 mils) min. | Depend on LME Price |
| UL Listed Copper Bonded Rod 3/4" x 8 ft (SGPCBR-1703) | 3/4" (17.2 mm shank) | 2.4 m | 254 µm (10 mils) min. | Depend on LME Price |
| UL Listed Copper Bonded Rod 3/4" x 10 ft (SGPCBR-1703) | 3/4" (17.2 mm shank) | 3.0 m | 254 µm (10 mils) min. | Depend on LME Price |
| UL Listed Copper Bonded Rod 20 mm x 10 ft (SGPCBR-2003) | 20 mm | 3.0 m | 254 µm (10 mils) min. | Depend on LME Price |
| UL Listed Copper Bonded Rod 25 mm x 3 m (SGPCBR-2503) | 25 mm | 3.0 m | 254 µm (10 mils) min. | Depend on LME Price |
Prices track the LME copper rate on the quotation date and are quoted ex-works per piece. * Prices are indicative. For the latest price, contact SG Power.
| Parameter | Value |
|---|---|
| Core | High-tensile, low-carbon steel |
| Copper | 99.9% pure electrolytic copper, molecularly bonded |
| Copper coating thickness | 254 microns (10 mils) minimum, the UL 467 requirement for listed ground rods |
| Threads | Rolled, not cut, to keep the copper layer intact |
| Standards | UL 467 Ed. 11 and CSA C22.2 No. 41:22 (UL listed, File No. E511876); also designed to IS 3043 and BS EN 62561-2 |
| Marking | UL mark, SG Power mark and size on each rod |
Custom lengths outside the listed range can be made, but they are not UL listed. We will say so clearly on the quotation.
Request a firm price for your bill of quantities. Send diameter, length and quantity; the offer includes the UL listing reference and datasheet for submittal.
UL listed rods are usually specified where the owner, consultant or code calls for third-party certified grounding.
| Sector | Why UL listing is specified |
|---|---|
| Data centres | Global operators apply one grounding specification across sites |
| Oil, gas and petrochemical | International EPC and owner specifications |
| Overseas projects executed by Indian EPCs | Required by US and many Middle East specifications |
| Multinational factories and campuses | Corporate engineering standards call for UL listed parts |
| Solar and renewable energy | Lender and owner technical specifications |
| Telecom and network sites | Operator grounding standards |
| Airports, metro and defence | Consultant specifications for critical infrastructure |
UL issued SG Power two Certificates of Compliance on 2 July 2024: one for the US market and one for Canada. Both name SG Power Products Pvt. Ltd. as the certificate holder and cover the same four copper bonded grounding rod models.
| Item | US certificate | Canada certificate |
|---|---|---|
| Certificate number | UL-US-L511876-11-41210202-2 | UL-CA-L511876-31-41210202-2 |
| UL category | KDER, Grounding and Bonding Equipment | KDER7, Grounding and Bonding Equipment Certified for Canada |
| Standard | UL 467, Edition 11, issue date 29 April 2022 | CSA C22.2 No. 41:22, 7th edition, issue date 29 April 2022 |
| Report reference | E511876-20201214 | E511876-20201214 |
| Models | SGPCBR-1403, SGPCBR-1703, SGPCBR-2003, SGPCBR-2503 | Same four models |
| Issued to | SG Power Products Pvt. Ltd., Plot No. 695-696, Duhai Industrial Area, Meerut Road, Ghaziabad, Uttar Pradesh 201206 | Same |
| Date | 2 July 2024 | 2 July 2024 |
File number (E511876). This is the number to search in UL Product iQ. The "L511876" inside the certificate number refers to the same file.
Category code. KDER is UL's category for grounding and bonding equipment, which includes ground rods. KDER7 is the same category certified for Canada.
Standard and edition. UL 467 Edition 11 (2022) is the current edition. A certificate citing an older edition is not wrong, but ask whether the listing has been updated.
Models. Only the listed models are certified. Match the model or size on your quotation to the certificate's model list.
Issued to. The company named should be the maker, or the brand your supplier is authorised to sell.
A certificate shows that representative samples passed UL testing. As the certificate itself states, the right to apply the UL mark comes from UL's follow-up services, and only rods that carry the UL mark count as UL certified. So check the certificate, then look for the mark on the rods delivered.
Check the listing yourself before you approve any supplier, including us.
Ask the supplier for its UL file number.
Search that number in UL Product iQ and confirm the company name and the category: KDER for the US, KDER7 for Canada.
Check that the diameter and length you are ordering are covered by the listing.
On delivery, check that each rod carries the UL mark, the maker's mark and the size.
SG Power's listing: UL File No. E511876, categories KDER and KDER7. Search E511876 in UL Product iQ.
A UL listed rod is only as reliable as the supplier's proof behind it. Use these six checks as a vendor evaluation checklist.
Verifiable UL listing. The file number (for SG Power, E511876) must be in the supplier's name (or the brand it supplies) in Product iQ, cover your exact diameters and lengths, and appear as a UL mark on every rod.
Manufacturer or authorised supplier. Buy from the listed manufacturer or a supplier it authorises in writing, so every batch stays traceable.
Copper bonding quality. The copper should not peel or crack when a rod is bent. Ask for the minimum copper thickness and the batch test certificate.
Listed accessories where required. If the specification asks for a fully listed system, couplers and clamps must be listed too.
Submittal-ready documents. UL listing, datasheet, test reports and material test certificates in a form your consultant accepts.
Stock, lead time and delivery. Ready stock of listed sizes, lead times for bulk orders and delivery to your site.
"UL 467 compliant" or "UL grade" with no file number
A file number that does not appear in Product iQ, or appears under another company with no authorisation
No UL mark on the rods delivered
A price far below other listed suppliers for the same size
Each production batch is checked against the UL listing and our quality plan before dispatch.
| Stage | Check | Record |
|---|---|---|
| Raw material | Steel grade and copper purity against mill certificates | Mill test certificate |
| Copper coating | Coating thickness against the 254-micron (10 mil) minimum | Batch thickness record |
| Bond adhesion | Bend test on samples from each batch | Test record |
| Dimensions | Diameter, length, thread and straightness | Inspection report |
| Marking | UL mark, maker's mark and size within the top 12 in (305 mm) | Visual check |
| Dispatch | Quantity, size and packing against the order | Packing list |
Quality plan: a project-specific QAP can be submitted for approval.
Third-party inspection: stage or pre-dispatch inspection by the client or its agency is accepted on agreed dates.
Quality system: ISO 9001:2015 certified quality management system for chemical earthing electrodes, copper bonded rods, earthing pit covers, earthing compound and lightning arresters. Certificate No. IN8514A, issued by Integral Certification (P) Ltd. (EGAC accredited, IAF MLA member).
| Criterion | SG Power |
|---|---|
| Business type | Manufacturer and direct supplier, with in-house manufacturing at Duhai Industrial Area, Ghaziabad, Uttar Pradesh |
| UL listing | UL File No. E511876: UL 467 (US, KDER) and CSA C22.2 No. 41 (Canada, KDER7); certificates dated 2 July 2024 |
| Quality management | ISO 9001:2015, Certificate No. IN8514A (Integral Certification (P) Ltd.) |
| Experience | 15+ years in earthing and lightning protection |
| Reference clients | Indian Railways, L&T, NTPC, BHEL, Tata, Adani Power, AAI |
| Documentation | UL listing, datasheet, test reports, MTC, QAP on request |
| Inspection | Client and third-party inspection accepted |
| Logistics | Pan-India delivery to project site, dispatched from our Ghaziabad factory (Delhi NCR), with support from our dealer and distributor network |
| Related supply | Couplers, clamps, backfill compound, earth pit covers, lightning protection |
| Registered office | 17th floor, The Iconic Corenthum, Sector 62, Noida, Uttar Pradesh 201309 |
| Factory (UL certified) | Plot No. 695-696, Duhai Industrial Area, Meerut Road, near HLM College, Ghaziabad, Uttar Pradesh 201206 |
Send your RFQ with the details below. We reply with a techno-commercial offer, a compliance statement against your specification, and the UL listing for submittal.
Project name, location and end client
Specification clause for grounding electrodes (attach if possible)
Rod diameter, length, type (threaded or pointed) and quantity
Couplers, clamps and driving studs required, and whether they must also be UL listed
Inspection requirements: QAP approval, stage or pre-dispatch TPI
Required delivery date and delivery address
Billing entity and GST number
| Term | Detail |
|---|---|
| Price basis | Ex-works Ghaziabad / FOR site, per piece |
| Taxes | GST extra at applicable rate |
| Payment | 50% Advance Payment |
| Document | What it proves | When you get it |
|---|---|---|
| UL certificates, File No. E511876 (US and Canada) | Rod is UL 467 and CSA C22.2 No. 41 listed | With the quotation |
| Product datasheet | Sizes, materials and specifications | With the quotation |
| Test reports | Copper bonding and mechanical tests | On request, for submittal |
| Material test certificate | Batch quality of the supplied rods | With dispatch |
| Packing list and invoice | Quantity and sizes shipped | With dispatch |
Technical statements on this page are based on the following standards and published sources: